Plan Review Notes For Permit 23031034
Permit Number 23031034
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-28 11:55:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THESE
 UNITS.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 THERE IS NO INDICATION OF WHAT IS EXISTING VS.
 PROPOSED.
  
 THERE IS NO PROPOSED OCCUPANCY CLASSIFICATION.
  
 THERE IS NO INDICATIONS OF SMOKE ALARM/FIRE ALARM.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THESE
 UNITS.
  
  
  
 2) THERE IS NO FLOOR PLAN OF THE 1ST & 2ND FLOORS
 INDICATING THE LOCATIONS OF THE ROOMS BEING REPAIRED.
  
 ARE THERE ANY UNITS THAT ARE NOT BEING REPAIRED?
  
 FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING
 THE LOCATIONS OF THE ROOMS.
  
  
  
 3) THERE ARE NO INDICATIONS OF THE PROPOSED FLOOR
 FINISHES THAT INDICATE MEETING THE REQUIREMENTS PER
 NFPA
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
  
 IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, NATURAL
 STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD NOT BE
 REQUIRED.
  
 IS THE FLOORING BEING INSTALLED UNDER A SEPARATE
 PERMIT?
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 4) THE APPLICATION INDICATES 3201 BROADWAY; HOWEVER,
 THE SUBMITTED PLAN SHEETS INDIATE 3205 BROADWAY.
  
 WHICH IS CORRECT AND PROVIDE FOR CORRECTIONS?
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  