| Date |
Text |
| 2023-03-28 11:55:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THESE |
| | UNITS. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | THERE IS NO INDICATION OF WHAT IS EXISTING VS. |
| | PROPOSED. |
| | |
| | THERE IS NO PROPOSED OCCUPANCY CLASSIFICATION. |
| | |
| | THERE IS NO INDICATIONS OF SMOKE ALARM/FIRE ALARM. |
| | |
| | PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THESE |
| | UNITS. |
| | |
| | |
| | |
| | 2) THERE IS NO FLOOR PLAN OF THE 1ST & 2ND FLOORS |
| | INDICATING THE LOCATIONS OF THE ROOMS BEING REPAIRED. |
| | |
| | ARE THERE ANY UNITS THAT ARE NOT BEING REPAIRED? |
| | |
| | FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING |
| | THE LOCATIONS OF THE ROOMS. |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF THE PROPOSED FLOOR |
| | FINISHES THAT INDICATE MEETING THE REQUIREMENTS PER |
| | NFPA |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| | CLASSIFICATION. |
| | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| | FINISHES SHALL |
| | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| | IGNITION |
| | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| | MATERIALS. |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| | THE CLASSES SPECIFIED |
| | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| | CRITICAL RADIANT FLUX |
| | REQUIREMENTS. |
| | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.45 W/CM2, AS DETERMINED |
| | BY THE TEST DESCRIBED IN 10.2.7.3. |
| | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.22 W/CM2, BUT LESS |
| | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| | 10.2.7.3. |
| | |
| | |
| | IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, NATURAL |
| | STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD NOT BE |
| | REQUIRED. |
| | |
| | IS THE FLOORING BEING INSTALLED UNDER A SEPARATE |
| | PERMIT? |
| | |
| | PLEASE REVIEW AND PROVIDE SPEC SHEETS. |
| | |
| | |
| | |
| | 4) THE APPLICATION INDICATES 3201 BROADWAY; HOWEVER, |
| | THE SUBMITTED PLAN SHEETS INDIATE 3205 BROADWAY. |
| | |
| | WHICH IS CORRECT AND PROVIDE FOR CORRECTIONS? |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |