| Plan Review Notes For Permit 23031016 |
| Permit Number |
23031016 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-21 09:26:14 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23031016 | | | 3/21/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) DRAWING PLM-001: PLEASE INDICATE HOW COMBUSTION AIR | | | WILL BE PROVIDED FOR THE COOKTOP, FIREPLACE AND DRYER- | | | SEC. G2407.1 FBC RES. IF USING THE STANDARD METHOD PER | | | SEC. G2407.5.1 THE MINIMUM REQUIRED VOLUME SHALL BE 50 | | | CU. FT. PER 1000 BTUH. CALCULATIONS ARE REQUIRED. | | | PLEASE SEC. G2407.1 EXCEPTION WHICH ALLOWS THE USE OF | | | MAKEUP AIR FOR THE DRYER. | | | | | | 2) PLM-001: PROVIDE A FIREPLACE VENTING DIAGRAM THAT | | | SHOWS THE TYPE AND SIZE OF VENT FLUE, THE VENT RUN | | | LENGTH AND TERMINATION LOCATION- SECS. G2427.1, | | | G2434.1, & G2435.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|