Plan Review Notes
Plan Review Notes For Permit 23031016
Permit Number 23031016
Review Stop G
Sequence Number 1
Notes
Date Text
2023-03-21 09:26:141ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23031016
 3/21/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DRAWING PLM-001: PLEASE INDICATE HOW COMBUSTION AIR
 WILL BE PROVIDED FOR THE COOKTOP, FIREPLACE AND DRYER-
 SEC. G2407.1 FBC RES. IF USING THE STANDARD METHOD PER
 SEC. G2407.5.1 THE MINIMUM REQUIRED VOLUME SHALL BE 50
 CU. FT. PER 1000 BTUH. CALCULATIONS ARE REQUIRED.
 PLEASE SEC. G2407.1 EXCEPTION WHICH ALLOWS THE USE OF
 MAKEUP AIR FOR THE DRYER.
  
 2) PLM-001: PROVIDE A FIREPLACE VENTING DIAGRAM THAT
 SHOWS THE TYPE AND SIZE OF VENT FLUE, THE VENT RUN
 LENGTH AND TERMINATION LOCATION- SECS. G2427.1,
 G2434.1, & G2435.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  