Plan Review Notes
Plan Review Notes For Permit 23030976
Permit Number 23030976
Review Stop B
Sequence Number 1
Notes
Date Text
2023-04-05 14:29:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SOME OF THE WORK THAT IS SPECIFIED FOR THIS PROJECT
 IS NOT IN SCOPE OF WORK THAT CAN BE DONE BY A PLUMBING
 CONTRACTOR. A FLORIDA LICENSED CBC OR CGC WILL HAVE TO
 APPLY FOR A SUB PERMIT FOR THIS PROJECT. FS 489
  
 2) THE VALUE SPECIFIED ON THE APPLICATION APPEARS TO BE
 LOW FOR THE SCOPE OF WORK. SUBMIT AN ITEMIZED COST
 BREAK DOWN FOR THE PROJECT. BUILDING PERMIT VALUATION.
 FOR PERMITTING PURPOSES, VALUATION OF FBC 109.3
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 3) SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE
 SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE
 DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 THE TEST REPORTS SHALL BE FROM AN APPROVED TESTING
 AGENCY. THE FOLLOWING TEST REPORTS SRE EQUIRED:
  
 A) FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 B) FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 C) FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
  
  