| 2023-04-19 06:34:24 | 1ST REVIEW FMC |
| | PERMIT: 230309651) |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) LABEL THE ROOM TO THE RIGHT OF THE ROOM WHERE THE |
| | HOOD WILL BE INSTALLED. THE HOOD DRAWING SUBMITTED |
| | LABELS THIS ROOM AS A TASTING ROOM. THE ORIGINAL |
| | DRAWINGS SHOW THIS TO BE A ROOM WHERE FERMENTING |
| | OCCURRED. WHAT WILL BE THE USE OF THIS SPACE? FBC |
| | 107.3.5 |
| | |
| | 2) SHEET 002 MECHANICAL PLAN INDICATES NEW |
| | REFRIGERATION. ADD A NOTE ON THE DRAWINGS TO STATES THE |
| | REFRIGERATION WORK WILL REQUIRE A COMPLETE REVIEW |
| | PACKAGE AND A SEPARATE PERMIT AS IT WILL NOT BE |
| | REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) THE SPACE WHERE THE BREWERY WAS LOCATED IS NOW A |
| | KITCHEN. PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS |
| | FOR THIS KITCHEN. FMC 403.3.1.1 |
| | |
| | 4) PROVIDE A ROOF DRAWING INDICATING THE LOCATION OF |
| | THE MECHANICAL SYSTEM THAT IS CONDITIONING THE KITCHEN |
| | AND TASTING ROOM. FBC 107.3.5 |
| | |
| | 5) PROVIDE AN AIR BALANCE REPORT FOR THIS RESTAURANT. |
| | FMC 508.1.2 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |