2023-04-19 06:34:241ST REVIEW FMC
 PERMIT: 230309651)
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LABEL THE ROOM TO THE RIGHT OF THE ROOM WHERE THE
 HOOD WILL BE INSTALLED. THE HOOD DRAWING SUBMITTED
 LABELS THIS ROOM AS A TASTING ROOM. THE ORIGINAL
 DRAWINGS SHOW THIS TO BE A ROOM WHERE FERMENTING
 OCCURRED. WHAT WILL BE THE USE OF THIS SPACE? FBC
 107.3.5
  
 2) SHEET 002 MECHANICAL PLAN INDICATES NEW
 REFRIGERATION. ADD A NOTE ON THE DRAWINGS TO STATES THE
 REFRIGERATION WORK WILL REQUIRE A COMPLETE REVIEW
 PACKAGE AND A SEPARATE PERMIT AS IT WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 3) THE SPACE WHERE THE BREWERY WAS LOCATED IS NOW A
 KITCHEN. PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS
 FOR THIS KITCHEN. FMC 403.3.1.1
  
 4) PROVIDE A ROOF DRAWING INDICATING THE LOCATION OF
 THE MECHANICAL SYSTEM THAT IS CONDITIONING THE KITCHEN
 AND TASTING ROOM. FBC 107.3.5
  
 5) PROVIDE AN AIR BALANCE REPORT FOR THIS RESTAURANT.
 FMC 508.1.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  