| 2023-03-31 09:18:00 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL2533-R28 SYSTEM NO. W-77 DOES NOT MEET THE |
| | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| | FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| | EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED SYSTEM |
| | 2. FBC B 107.2.1. APPROVED PLANS SHEET A-02 NORTH & |
| | EAST ELEVATION DRAWING DETAILS SHOWS CLAY TILE ROOF & |
| | AWNING OVERHANGS. PLEASE PROVIDE THE FOLLOWING FOR THE |
| | TILE ROOF INSTALLATION; 2020 CODE VERSION PRODUCT |
| | APPROVAL/ NOA???S FOR THE ROOF TILE SYSTEM; ROOF |
| | UNDERLAYMENT SYSTEM; PROVIDE METHOD OF INSTALLATION, IF |
| | USING ADHESIVE SET PROVIDE 2020 CODE VERSION PRODUCT |
| | APPROVAL/ NOA???S. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. |
| | 3. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| | APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| | PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| | SUBMITTING. REVIEW STAMP WITH INITIALS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |