| Plan Review Notes For Permit 23030911 |
| Permit Number |
23030911 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-06-21 13:09:44 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC R 301.1, PROVIDE ENGINEER APPROVED GENERATOR SLAB | | | AND TIE-DOWN CONNECTION DETAILS THAT MEET THE WINDLOAD | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE. | | | FBC B 107.2.1, PROVIDE GENERATOR SET BACK DISTANCE FROM | | | HOUSE (OPERABLE OPENINGS) ON SURVEY. |
|