| Date |
Text |
| 2023-03-16 12:49:50 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL10497-R8 HAS BEEN |
| | REVISED TO FL10497-R9. PLEASE PROVIDE THE FOLLOWING: |
| | INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-4 AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR |
| | PRODUCT APPROVAL FL10497-R8 SYSTEM NO. W-156 DO NOT |
| | MEET THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF |
| | -108.17 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM |
| | THAT MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS |
| | FOR EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | AS PER RULE 61G20-3. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |