| Plan Review Notes For Permit 23030823 |
| Permit Number |
23030823 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-04-24 11:43:03 | 1ST REVIEW FMC | | | PERMIT: 23030823 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY CALCULATIONS SUBMITTED ARE FOR 2 | | | MECHANICAL SYSTEMS, 1- KITCHEN DINING ROOMS; SYSTEM 2- | | | MASTER SUITE. THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS ARE FOR 4 SYSTEMS. THE GARAGE IN THE | | | EQUIPMENT WAS NOT INCLUDED IN THE ENERGY CALCULATIONS. | | | PROVIDE ENERGY CALCULATIONS FOR THE GARAGE AND INCLUDE | | | THE GARAGE DOOR. FRC R101.5.1.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|