| Date |
Text |
| 2023-05-31 09:11:54 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23030803 |
| | 5/31/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST |
| | REVIEW COPIED BELOW WAS NOT ADDRESSED- P;LEASE COMPLY. |
| | |
| | 1) SHEETS P-100 & C1.2: THE PLANS SHOW A NEW WATER |
| | SERVICE BACKFLOW PREVENTER AND A NEW 1500 GALLON GREASE |
| | INTERCEPTOR TO BE INSTALLED. PLEASE NOTE SEPARATE |
| | PERMITS ARE REQUIRED FOR EACH AND APPLICATIONS FOR EACH |
| | SHALL BE SUBMITTED PRIOR TO APPROVAL OF THE PLUMBING |
| | REVIEW. AT THIS TIME APPLICATIONS CAN BE SUBMITTED AS |
| | TBD (TO BE DETERMINED) IF CONTRACTORS ARE CURRENTLY NOT |
| | SELECTED. PLEASE EMAIL THE APPLICATIONS TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |