Plan Review Notes
Plan Review Notes For Permit 23030803
Permit Number 23030803
Review Stop B
Sequence Number 2
Notes
Date Text
2023-05-31 11:42:07WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23030803
 ADD: 439 7TH ST.
 CONT: HEDRICK BROTHERS CONSTRUCTION
 TEL: 561-308-2954
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY APRIL 03RD/ 2023
 SHELL BUILDING REMODEL & ADDITION PLUS STEEL FRAMING
 FOR FUTURE DECORATIVE METAL PRE-ENGINEERED GRIDWORK
 (NOTE 2 SHEET A.301).
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SEMI-COMPLIED. IN RESPONSE TO THE DESIGNER OF
 RECORD, THIS CODE SECTION 1018.5 ACCESS TO PUBLIC WAY
 IS VERY RELEVANT. HOW DO YOU MAINTAIN ACCESS TO THE
 PUBLIC WAY IF VEHICLES ARE PARKED OR UNLOADING IN FRONT
 OF THE ALCOVE, THE CODE SECTION STATES DIRECT AND
 UNOBSTRUCTED, WE HAVE THIS SAME PROBLEM WHEN BUILDING
 ARE BUILT TO THE LOT LINE AND ALLEY DIRECTLY BEHIND THE
 BUILDING. PLEASE LET US KNOW HOW THE PETITION IS GOING
 FOR THE NO PARKING SIGNS, THERE SHOULD BE SOME
 LANGUAGE, AS TO WORDING, FONT SIZE AND SIGN SIZE, THANK
 YOU.
 SHEET A.101 & SHEET A.100 THE SITE PLOT PLAN SHOWS THE
 2ND MEANS OF EGRESS THROUGH DOORS 105 & 102.
 DOOR 102 IS RECESSED BACK IN A NEWLY BUILT ALCOVE BUT
 THERE IS ONLY 6 INCHES TO THE PROPERTY LINE HOW WILL
 YOU KEEP FROM HAVING TRUCKS STOPPING AND PARKING,
 UNLOADING IN FRONT OF THE ALCOVE. 2020 FBC-BUILDING
 CODE SECTION 1028.5 ACCESS TO A PUBLIC WAY. THE EXIT
 DISCHARGE SHALL PROVIDE A DIRECT AND UNOBSTRUCTED
 ACCESS TO A PUBLIC WAY.
  
 4) 2ND REQUEST. THE RESPONSE LETTER STATES THIS PROJECT
 IS A SHELL PERMIT ONLY. THE PERMIT APPLICATION STATES
 RENOVATION, THE TITLEBLOCK STATES EXISTING BUILDING
 ALTERATION & ADDITION FOR NORA PHASE I NOWHERE IS IT
 STATED THE SCOPE OF THIS PERMIT IS A SHELL.
 SHEET A.101 & S.101PLEASE SHOW BOTH DOORS 101A & 102 AS
 EXIT DOORS WILL BE ACCESSIBLE EXITS. 2020
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 DOOR 102 IS A NEW BUILDING ELEMENT. 2020 EXISTING
 BUILDING CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING & ACCESSIBILITY CODE.
  
 5) SEMI-COMPLIED. SHEET A.101 STILL SHOWS THE DOOR 102
 LANDING PAST THE PROPERTY LINE.
 1ST ROUND COMMENTS. SHEET S.101 REAR DOOR NEW FLOOR
 SLAB PROJECTS PAST THE PROPERTY LINE. SEE SITE PLOT
 PLAN. DISCREPANCY IN PLANS. 107.2.1. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 6) 2ND REVIEW. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "CODE SECTIONS SHALL
 NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION".
 1ST ROUND OF COMMENTS. SHEETS A.101 & A.501 SECTION 2
 INDICATE NOTE # 20 NEW IMPACT RATED GLASS SECTIONAL
 GARAGE DOORS, FULLY GLAZED MUST MEET THE REQUIREMENTS
 SLOPED GLAZING SECTIONS 2405.1 & 2405.2 OF THE 2020
 FBC-BUILDING CODE.
  
 7) 2ND REQUEST. NOTES EVEN IF GENERAL NOTES SHOULD
 RELATE TO THE PLAN AT HAND. THE BUILDING IS TYPE II
 CONSTRUCTION, AND THE NOTE IS TALKING ABOUT PLYWOOD AND
 FASTENERS FOR PLYWOOD. THAT IS WHY I INDICATED IF
 PLYWOOD IS TO BE INSTALLED, THEN THE NOTE SHOULD READ
 FIRE RETARDANT TREATED PLYWOOD.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 1ST ROUND COMMENTS. SHEET A.101 FRAMING FASTENER NOTES
 SPEAK OF PLYWOOD AND FASTENERS, THERE IS NO MENTION OF
 THE REQUIREMENT FOR FIRE RETARDANT TREATED PLYWOOD. THE
 TITLE SHEET LIST THIS BUILDING TYPE AS II-B
 CONSTRUCTION. PLEASE REVIEW SECTION 603.3.1.1 FIRE
 RETARDANT TREATED WOOD.
  
 8) SHEET S.401 & S.402 SHOWS WELDING IN DETAILS OF BAR
 JOIST AND ROOF DECKING:
 BUILING PROVISO: WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 9) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. PLEASE
 SUBMIT THE COMPONENTS AND CLADDING PRODUCT APPROVALS.
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 12) COMPLIED.
  
  
 13) 2ND REQUEST, PLEASE PROVIDE THE PRESSURES IN VASD
 SINCE ALL PRODUCT APPROVALS ARE IN VASD.
  
 1ST ROUND COMMENTS. SHEET S.003 COMPONENTS AND CLADDING
 PRESSURES DO NOT STATE IF THEY ARE IN VULT OR VASD.
 PLEASE PROVIDE PRESSURES IN VASD SINCE PRODUCT
 APPROVALS ARE ALL IN VASD. THANK YOU. NOTE 2 STATES
 VULT.
  
 14) COMPLIED.
  
 15) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
2023-05-31 09:54:25IN REVIEW 05/31/23 J WITMER