| 2023-04-28 14:25:34 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23030802 |
| | 4/28/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-1 & P-3: DRAINAGE FROM HAND SINKS AND FLOOR |
| | SINKS BELOW ICE BINS AND ICE MAKERS SHALL NOT DISCHARGE |
| | INTO THE GREASE WASTE INTERCEPTOR- SEC. 1003.3.1 FBC P. |
| | THIS INCLUDES THE DRAINAGE FROM HAND SINKS AND FLOOR |
| | SINKS IN THE OUTDOOR BAR. PLEASE ROUT THE DRAINAGE TO |
| | THE SANITARY SEWER. |
| | |
| | 2) P-1: PLEASE PROVIDE A SANITARY DRAINAGE AND VENT |
| | ISOMETRIC DRAWING- SEC. 107.3.5.1.3 WPB. |
| | |
| | 3) P-2 & P-3: PROVIDE BACKFLOW PREVENTERS ON WATER |
| | SUPPLY LINES TO THE STEAMER, DISHWASHER, AND |
| | GLASSWASHER- SEC. 608.3 FBC P. |
| | |
| | 4) P-2 & P-3: INDICATE THE MEANS OF PROVIDING TEMPERED |
| | WATER DELIVERY FROM THE LAVATORY SINKS AS REQUIRED BY |
| | SEC. 419.5 FBC P. |
| | |
| | 5)P-2 & P-3: PLEASE VERIFY THERE IS AN EXISTING HOT |
| | WATER TEMPERATURE LIMITING DEVICE SUCH AS A MASTER |
| | THERMOSTATIC MIXING VALVE AT THE WATER HEATER, OR |
| | PROVIDE ONE IN COMPLIANCE WITH SEC. 607.1.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |