| Plan Review Notes For Permit 23030802 |
| Permit Number |
23030802 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-10 14:25:22 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PANEL CB AND CIRCUITS FED BY THAT PANEL 48,50,52 | | | WITHIN 6' OF THE SINK, 1,3 NOT SURE IF FED BY A | | | RECPTACLE. TO BE GFCI PROTECTED. 210.8(B) NEXT TO SINK | | | (6') | | | | | | 2) PANEL CC CIRCUITS 13,14,15,17,19,23,25,32 ALSO NEED | | | TO BE GFCI PROTECTED 210.8(B) OUTSIDE | | | | | | |
|