| 2023-05-02 15:28:28 | RESTAURANT REMODEL AND ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, |
| | LOUVERS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS |
| | NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD FBC 107.3.4 |
| | |
| | 2) PLEASE SHOW THE ACCESSIBLE BAR SEATING COUNTER |
| | HEIGHT, CLEAR FLOOR SPACE AND KNEE AND TOE CLEARANCE - |
| | FBC A 902 |
| | |
| | 3) PLEASE SHOW THE ACCESSIBLE SEATING, COUNTER HEIGHT, |
| | CLEAR FLOOR SPACE, KNEE AND TOE CLEARANCE AT THE "SUSHI |
| | BAR" - FBC A 902 |
| | |
| | 4) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS |
| | "REFLECTIVE SURFACE" WHEN REFERRING TO THE MIRROR |
| | DIMENSIONS FROM THE FLOOR - FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5) PLEASE PROVIDE DETAILS FOR THE ROOF TOP EQUIPMENT |
| | SCREENING (SHOWING ALL ATTACHMENTS) - FBC 1609 |
| | |
| | 6) PLEASE SHOW THE ATTIC VENTILATION DETAILS - FBC |
| | 1203.2 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH |
| | SEPARATE SPACE BY VENTILATION OPENINGS PROTECTED |
| | AGAINST THE ENTRANCE OF RAIN AND SNOW. |
| | |
| | 7) PLEASE PROVIDE A BUILDING ONLY APPRAISAL FOR THIS |
| | BUILDING - NEEDED TO DETERMINE IF THE ADDITION AND |
| | REMODEL IS A SUBSTANTIAL IMPROVEMENT - FBC EXISTING |
| | BUILDING1103.5 |
| | |
| | 8) DRAWINGS A-12, A-13 AND A-14 DO NOT SHOW AS |
| | DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| | DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |