Plan Review Notes
Plan Review Notes For Permit 23030724
Permit Number 23030724
Review Stop B
Sequence Number 2
Notes
Date Text
2023-04-21 13:21:19REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A501 - DETAIL W4 SAYS "OPERABLE DOOR" - -
 PLEASE SHOW THE EXTERIOR LANDING FOR THE ADDED DOOR TO
 COMPLY WITH - FBC 1010.1.5 FLOOR ELEVATION.
 THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF A
 DOOR. SUCH FLOOR OR LANDING SHALL BE AT THE SAME
 ELEVATION ON EACH SIDE OF THE DOOR. LANDINGS SHALL BE
 LEVEL EXCEPT FOR EXTERIOR LANDINGS, WHICH ARE PERMITTED
 TO HAVE A SLOPE NOT TO EXCEED 0.25 UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE).
  
 FBC 1010.1.6 LANDINGS AT DOORS.
 LANDINGS SHALL HAVE A WIDTH NOT LESS THAN THE WIDTH OF
 THE STAIRWAY OR THE DOOR, WHICHEVER IS GREATER. DOORS
 IN THE FULLY OPEN POSITION SHALL NOT REDUCE A REQUIRED
 DIMENSION BY MORE THAN 7 INCHES (178 MM). WHERE A
 LANDING SERVES AN OCCUPANT LOAD OF 50 OR MORE, DOORS IN
 ANY POSITION SHALL NOT REDUCE THE LANDING TO LESS THAN
 ONE-HALF ITS REQUIRED WIDTH. LANDINGS SHALL HAVE A
 LENGTH MEASURED IN THE DIRECTION OF TRAVEL OF NOT LESS
 THAN 44 INCHES (1118 MM).
  
 2) PLEASE PROVIDE A SURVEY SHOWING THE PROPERTY LINES -
 FBC 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.