| Plan Review Notes For Permit 23030626 |
| Permit Number |
23030626 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-05-16 10:37:17 | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 23030626 | | | 5/11/2023 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED RISER DOES NOT SHOW THE GAS PIPE SIZES- | | | SEC. G2413.3 FBC RES. | | | | | | 2) 2ND REQUEST. P-1: PROVIDE COMBUSTION AIR | | | CALCULATIONS FOR THE RANGE- SEC. G2407.1. IF USING THE | | | STANDARD METHOD PLEASE NOTE THE MINIMUM REQUIRED ROOM | | | VOLUME SHALL BE 50 CU.FT. PER 1000 BTUH OF THE | | | APPLIANCE INPUT RATING- SEC. G2407.5.1 WPB. | | | | | | 3) 2ND REQUEST. P-1: THE PRINTED NAME AND SIGNATURE OF | | | THE LICENSED GAS CONTRACTOR OR QUALIFIER SHALL BE ON | | | THE DRAWING- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|