Plan Review Notes
Plan Review Notes For Permit 23030626
Permit Number 23030626
Review Stop G
Sequence Number 1
Notes
Date Text
2023-05-01 07:39:49 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23030626
 5/1/2023
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-1: THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE
 FOLLOWING INFORMATION IN ACCORDANCE WITH SEC. 107.3.5.3
 WPB AND SEC. G2413.1 FBC RES.
  
 A) BRANCH AND CUT PIPE LENGTH MEASUREMENTS AND THE
 TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO
 THE TANKLESS WATER HEATER.
 B) INDIVIDUAL WATER HEATER AND RANGE BTU LOADS AND
 TOTAL BTU LOAD OF THE SYSTEM.
 C) TYPES OF PIPING.
 D) SYSTEM PRESSURE AT THE METER AND THE PRESSURES FROM
 THE REGULATORS TO THE APPLIANCES.
 E) PIPE SIZING TABLES.
  
 2) P-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE- SEC. G2407.1. IF USING THE STANDARD METHOD
 PLEASE NOTE THE MINIMUM REQUIRED ROOM VOLUME SHALL BE
 50 CU.FT. PER 1000 BTUH OF THE APPLIANCE INPUT RATING-
 SEC. G2407.5.1 WPB.
  
 3) P-1: THE PRINTED NAME AND SIGNATURE OF THE LICENSED
 GAS CONTRACTOR OR QUALIFIER SHALL BE ON THE DRAWING-
 SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  