| | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23030626 |
| | 5/1/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P-1: THE GAS RISER IS INCOMPLETE. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION IN ACCORDANCE WITH SEC. 107.3.5.3 |
| | WPB AND SEC. G2413.1 FBC RES. |
| | |
| | A) BRANCH AND CUT PIPE LENGTH MEASUREMENTS AND THE |
| | TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO |
| | THE TANKLESS WATER HEATER. |
| | B) INDIVIDUAL WATER HEATER AND RANGE BTU LOADS AND |
| | TOTAL BTU LOAD OF THE SYSTEM. |
| | C) TYPES OF PIPING. |
| | D) SYSTEM PRESSURE AT THE METER AND THE PRESSURES FROM |
| | THE REGULATORS TO THE APPLIANCES. |
| | E) PIPE SIZING TABLES. |
| | |
| | 2) P-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | RANGE- SEC. G2407.1. IF USING THE STANDARD METHOD |
| | PLEASE NOTE THE MINIMUM REQUIRED ROOM VOLUME SHALL BE |
| | 50 CU.FT. PER 1000 BTUH OF THE APPLIANCE INPUT RATING- |
| | SEC. G2407.5.1 WPB. |
| | |
| | 3) P-1: THE PRINTED NAME AND SIGNATURE OF THE LICENSED |
| | GAS CONTRACTOR OR QUALIFIER SHALL BE ON THE DRAWING- |
| | SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |