Plan Review Notes
Plan Review Notes For Permit 23030616
Permit Number 23030616
Review Stop Z
Sequence Number 1
Notes
Date Text
2023-04-13 16:46:004/13/23- FAILED. PLEASE PROVIDE THE FOLLOWING:
 1. INDICATE ON A SITE PLAN/SURVEY THE MAX HEIGHT OF THE
 WALL FROM THE EXISTING GRADE FOR ALL PROPERTY LINES.
 THE WALL ALONG ADJACENT TO FLALGER DRIVE CAN NOT EXCEED
 6 FEET IN HEIGHT AND THE WALL ADJACENT TO ESSEX CT CAN
 NOT EXCEED 4 FEET IN HEIGHT FOR THE FIRST 25 FEET.
 2. INDICATE THE SETBACKS FOR THE FOUNDATION FROM THE
 EXISTING PROPERTY LINE.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]