| Plan Review Notes For Permit 23030611 |
| Permit Number |
23030611 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-14 08:18:28 | 1ST REVIEW FMC | | | PERMIT: 23030611 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE GARAGE CONVERSION IS A CHANGE OF USE AND | | | THEREFORE AN ENERGY CALCULATION IS REQUIRED. FEC | | | R101.5.1.1.1 | | | | | | 2) IDENTIFY THE MECHANICAL SYSTEM ON THE FIRST FLOOR | | | AND SHOW ITS LOCATION ON THE DRAWING. FBC 107.3.5 | | | | | | 3) SHOW THE OPERABLE WINDOW IN THE BATHROOM ON THE MAIN | | | HOUSE 1ST FLOOR MEETS THE AGGREGATE AREA OF 3 SQUARE | | | FEET TO EXEMPT AN EXHAUST FAN. FRC R303.3 | | | | | | 4) PROVIDE DETAILS FOR THE KITCHEN RANGE. IS THIS A | | | BROILER COOKTOP? IS THERE TO BE A HOOD ABOVE THIS | | | COOKTOP? IF SO, PROVIDE THE CFMS OF THE HOOD MOTOR. FRC | | | M1503.4 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|