| Plan Review Notes For Permit 23030576 |
| Permit Number |
23030576 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-09 12:22:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED LOCATION OF THE PULL STATION DOES NOT | | | APPEAR TO WITHIN 5' OF THE EXIT DOOR. | | | | | | PER NFPA 72 | | | | | | 17.14 MANUALLY ACTUATED ALARM-INITIATING DEVICES | | | | | | 17.14.8.4 MANUAL FIRE ALARM BOXES SHALL BE LOCATED | | | WITHIN 5 FT | | | (1.5 M) OF EACH EXIT DOORWAY ON EACH FLOOR | | | | | | PLEASE PROVIDE DIMENSIONS IN COMPLIANCE OR RELOCATE | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|