Plan Review Notes
Plan Review Notes For Permit 23030576
Permit Number 23030576
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-09 12:22:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED LOCATION OF THE PULL STATION DOES NOT
 APPEAR TO WITHIN 5' OF THE EXIT DOOR.
  
 PER NFPA 72
  
 17.14 MANUALLY ACTUATED ALARM-INITIATING DEVICES
  
 17.14.8.4 MANUAL FIRE ALARM BOXES SHALL BE LOCATED
 WITHIN 5 FT
 (1.5 M) OF EACH EXIT DOORWAY ON EACH FLOOR
  
 PLEASE PROVIDE DIMENSIONS IN COMPLIANCE OR RELOCATE
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  