2023-06-27 09:19:371ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - THE GREASE INTERCEPTOR
 IS A STAND ALONE PERMIT AND REQUIRES ITS OWN DOCUMENTS.
 PLEASE SUBMIT THE SITE PLAN THE SHOWS THE LOCATION OF
 THE GREASE INTERCEPTOR.
  
 2. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE INCLUDE THE
 CALCULATIONS FOR THE INTERCEPTOR'S SIZING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  