| 2023-04-10 08:55:08 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-23030516 |
| | 4/10/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. IMPORTANT NOTE. THE |
| | FOLLOWING REVIEW IS FOR PLUMBING ONLY. A SEPARATE |
| | TENANT BUILD-OUT PERMIT FOR THE COMMERCIAL KITCHEN |
| | AND/OR NEW RESTAURANT IS REQUIRED. |
| | |
| | 1) THE NEW PLUMBING DRAWINGS ARE NOT IN COMPLIANCE WITH |
| | THE FOLLOWING FPC-2020 CODE SECTIONS. |
| | |
| | A) SEC. 910.1 & 1003.3.5: AS NOTED IN THE 1ST REVIEW, A |
| | TRAP AND VENT ARE REQUIRED FOR THE 3-COMPARTMENT SINK. |
| | MANUFACTURER???S INSTALL GUIDELINES FOR THE SCHIER GB-1 |
| | SHOW SINK TRAP AND VENT UPSTREAM OF THE INTERCEPTOR. |
| | B) SEC. 918.8: AN AAV SHALL NOT BE USED TO VENT THE |
| | GREASE TRAP. |
| | C) SEC. 904.1: THE BUILDING DRAIN REQUIRES NOT LESS |
| | THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS. |
| | D) SEC. 608.3: A BACKFLOW PREVENTER IS REQUIRED FOR THE |
| | WATER SUPPLY LINE TO THE ICE MAKER. |
| | E) SEC. 801.2: AN INDIRECT WASTE RECEPTOR IS REQUIRED |
| | TO RECEIVE THE DRAINAGE FROM THE ICE MAKER. |
| | |
| | 2) PLEASE NOTE OTHER LICENSING AGENCIES SUCH AS THE PB |
| | DEPARTMENT OF HEALTH, DBPR FOOD AND BEVERAGE LICENSING |
| | DEPT. OR DEPT. OF AGRICULTURE MAY REQUIRE A FLOOR DRAIN |
| | IN THE KITCHEN FOR SANITARY PURPOSES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |