| 2023-04-26 15:12:24 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM INCLUDING |
| | ELECTRICAL EQUIPMENT, CONDUIT, CONDUCTOR AND |
| | OVERCURRENT PROTECTION SIZES. NEC 215.5 |
| | |
| | 215.5 DIAGRAMS OF FEEDERS. |
| | IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A |
| | DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR |
| | TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM |
| | SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR |
| | OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL |
| | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE |
| | DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING |
| | DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO |
| | BE USED. |
| | |
| | 2) PLEASE PROVIDE A SITE PLAN LOCATING ALL ELECTRICAL |
| | EQUIPMENT. FBC 107.2 |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |