2023-03-10 09:52:111ST REVIEW FMC
 PERMIT: 23030471
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A SEPARATE MECHANICAL SUB-PERMIT WILL BE REQUIRED
 FOR THE INSTALLATION OF THE COOKTOP/OVEN DOWN-DRAFT.
  
 2) PROVIDE A MECHANICAL DRAWING SHOWING THE DUCTWORK
 AND TERMINATION LOCATION FOR THE DUCTWORK OF THE
 DOWN-DRAFT. FMC 505.1
  
 3) PROVIDE THE MAKE-UP AIR FOR THIS DOWN-DRAFT EXHAUST.
 FMC 505.2
  