| 2023-03-10 09:52:11 | 1ST REVIEW FMC | | | PERMIT: 23030471 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) A SEPARATE MECHANICAL SUB-PERMIT WILL BE REQUIRED | | | FOR THE INSTALLATION OF THE COOKTOP/OVEN DOWN-DRAFT. | | | | | | 2) PROVIDE A MECHANICAL DRAWING SHOWING THE DUCTWORK | | | AND TERMINATION LOCATION FOR THE DUCTWORK OF THE | | | DOWN-DRAFT. FMC 505.1 | | | | | | 3) PROVIDE THE MAKE-UP AIR FOR THIS DOWN-DRAFT EXHAUST. | | | FMC 505.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|