| 2023-03-31 10:46:45 | PLEASE RESPOND TO EACH COMMENT FROM THE ORIGINAL REVIEW | | | COMMENT. THERE ARE NO ROOM LABELS OR DOORS SHOW ON THIS | | | DRAWING. I HAVE NO WAY OF KNOWNING IF THE RETURN AIR | | | FROM EACH ROOM WILL MAKE IT BACK TO THE AHU. I CANNOT | | | APPROVE THIS DRAWING UNTIL THE THINGS I'VE ASKED FOR | | | ARE ON THE DRAWING. ALSO A BUSINESS CARD LAYING ON THE | | | DRAWING IS NOT THE DESIGNERS NAME AND SIGNATURE. SEE | | | FIRST REVIEW CYCLE COMMENTS BELOW: | | | | | | PROVIDE A DRAWING THAT SHOWS THE RETURN AIR PATH FROM | | | EACH ROOM BACK TO THE AHU. LABEL ALL ROOMS ON THIS | | | DRAWING.THERE ARE ROOMS SHOWN ON THIS DRAWING THAT HAVE | | | NO DUCTWORK. THERE IS A ROOM THAT DOES NOT SHOW A DOOR | | | OR A RETURN AIR TRANSFER. FMC 107.3.5 | | | THE DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR | | | NAME ON THE DRAWING. FBC AMENDMENT 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|