2023-03-31 10:46:45PLEASE RESPOND TO EACH COMMENT FROM THE ORIGINAL REVIEW
 COMMENT. THERE ARE NO ROOM LABELS OR DOORS SHOW ON THIS
 DRAWING. I HAVE NO WAY OF KNOWNING IF THE RETURN AIR
 FROM EACH ROOM WILL MAKE IT BACK TO THE AHU. I CANNOT
 APPROVE THIS DRAWING UNTIL THE THINGS I'VE ASKED FOR
 ARE ON THE DRAWING. ALSO A BUSINESS CARD LAYING ON THE
 DRAWING IS NOT THE DESIGNERS NAME AND SIGNATURE. SEE
 FIRST REVIEW CYCLE COMMENTS BELOW:
  
 PROVIDE A DRAWING THAT SHOWS THE RETURN AIR PATH FROM
 EACH ROOM BACK TO THE AHU. LABEL ALL ROOMS ON THIS
 DRAWING.THERE ARE ROOMS SHOWN ON THIS DRAWING THAT HAVE
 NO DUCTWORK. THERE IS A ROOM THAT DOES NOT SHOW A DOOR
 OR A RETURN AIR TRANSFER. FMC 107.3.5
 THE DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR
 NAME ON THE DRAWING. FBC AMENDMENT 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  