| Plan Review Notes For Permit 23030444 |
| Permit Number |
23030444 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-22 08:34:35 | PROVIDE A DRAWING THAT SHOWS THE RETURN AIR PATH FROM | | | EACH ROOM BACK TO THE AHU. LABEL ALL ROOMS ON THIS | | | DRAWING.THERE ARE ROOMS SHOWN ON THIS DRAWING THAT HAVE | | | NO DUCTWORK. THERE IS A ROOM THAT DOES NOT SHOW A DOOR | | | OR A RETURN AIR TRANSFER. FMC 107.3.5 | | | THE DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR | | | NAME ON THE DRAWING. FBC AMENDMENT 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|