Plan Review Notes
Plan Review Notes For Permit 23030384
Permit Number 23030384
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-28 09:54:07 
 1ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: EXPEDITED REVIEW FEES HAVE BEEN APPLIED. CT
  
 1.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVALS FOR THE PROPOSED SLIDING GLASS DOORS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2.PROVIDE A WINDOW AND DOOR FLASHING DETAIL OR THE
 SPECIFICATION SHEETS OF A LIQUID APPLIED MEMBRANE.
 FBC R 703.4, FBC B 1405.4:
 A FLASHING DETAIL OR SPECIFICATION IS REQUIRED. THIS
 COMMENT CAN BE RESOLVED BY DOING ONE OF THE FOLLOWING:
  
 REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED
 AND NOTE THE CODE REFERENCE FBC R 703.4; FBC B 1405.4:
 EXAMPLE "FLASHING IN ACCORDANCE WITH FBC R 703.4/B
 1405.4 WILL BE INSTALLED".
 PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS
 MAY INCLUDE MORE THAN ONE OPTION
 PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN
 ONE
 OPTION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  