| Date |
Text |
| 2023-05-17 14:34:07 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-23030381 |
| | 5/17/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLAN REVIEW RESULTS: |
| | DENIED. FAILED 1ST REVIEW COMMENTS #1, 2, 6A, 9, & 11 |
| | ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SHEET P100- IMPORTANT NOTE: SEPARATE PERMITS |
| | ARE REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER AND THE GREASE INTERCEPTOR, AND PERMIT |
| | APPLICATIONS FOR EACH SHALL BE SUBMITTED PRIOR TO |
| | APPROVAL OF THE MAIN PLUMBING PLANS FOR THE PROJECT. |
| | YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE CONTRACTORS SELECTED BY EMAILING |
| | COMPLETED PERMIT APPLICATIONS TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | THE ARCHITECT'S COMMENT RESPONSE NARRATIVE STATES THE |
| | BACKFLOW AND GREASE INTERCEPTOR ARE INLCLUDED IN A |
| | STREET IMPROVEMENT PERMIT HOWEVER AS STATED BELOW |
| | SEPARATE BUILDING DEPARTMENT PERMITS ARE REQUIRED. |
| | |
| | 2) FAILED. P-100 & P-200: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS FOR THE NEW BUILDING IN ACCORDANCE WITH |
| | TABLE 403.1 FBC P. PROVIDE SCHEDULES THAT SHOW THE |
| | REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR EACH |
| | SEPARATE OCCUPANCY OR TENANT SPACE. THE CALCULATIONS |
| | SHALL CLARIFY WHICH TENANT SPACES WILL ARE BEING |
| | SERVICED BY THE NEW GANG BATHROOMS, DRINKING FOUNTAINS |
| | AND JANITOR???S SINK. |
| | NO CALCULATIONS PROVIDED. THE ENGINEER???S RESPONSE |
| | NARRATIVE STATES THE INDOOR RESTROOMS ARE FOR THE |
| | OUTDOOR SPACES WHICH ARE NOT SHOWN ON THE PLANS AND NOT |
| | INCLUDED IN THE OCCUPANT LOAD CALCULATIONS ON SHEET |
| | T.100. PLEASE COMPLY WITH THE COMMENT. |
| | |
| | |
| | 6) FAILED ITEM A BELOW. P-700: THE SANITARY RISER |
| | APPEARS TO SHOW IMPROPER WET-VENTING FOR THE MEN???S |
| | AND WOMEN???S BATHROOM FIXTURES PER ITEMS A-D BELOW. |
| | |
| | A) FAILED. URINALS ARE NOT INCLUDED IN THE DEFINITION |
| | OF A BATHROOM GROUP SO THEIR FIXTURE DRAINS SHALL NOT |
| | CONNECT TO THE WET VENT, AND THEIR DRY VENTS SHALL NOT |
| | BE THE DRY VENT FOR THE SYSTEM- SECS. 202 & 912.1 FBC |
| | P. IN ORDER TO FIX THE BRANCH, THE URINAL DRAINS SHALL |
| | CONNECT DOWNSTREAM OF THE L2/WC-1 WET VENT, AND A |
| | COMMON VENT OR INDIVIDUAL VENTS FOR THE URINALS SHALL |
| | BE PROVIDED- SECS. 910.1 & 911.1. |
| | TO MEET THE CODE PLEASE PROVIDE INDIVIDUAL VENTS FOR |
| | THE URINALS. |
| | |
| | 9) FAILED. P-700: TEMPERED WATER SHALL BE DELIVERED |
| | FROM THE LAVATORIES THROUGH A WATER TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070- SECS. 419.5 |
| | & 607.1.2 FBC P. |
| | NOT PROVIDED. |
| | |
| | 11) FAILED. P-500: PLEASE PROVIDE A WATER HEATER DETAIL |
| | THAT SHOW THE PIPING CONNECTIONS TO THE RECIRCULATION |
| | PUMP, REQUIRED EXPANSION TANK AND THE REQUIRED MASTER |
| | THERMOSTATIC MIXING VALVE- SECS. 607.2.2 & 607.3 FBC P. |
| | PLEASE NOTE THE MASTER MIXING VALVE IS REQUIRED BECAUSE |
| | THE THERMOSTAT ON THE WATER HEATER CANNOT BE THE |
| | TEMPERATURE LIMITING MEANS FOR THE HOT WATER SYSTEM- |
| | SEC. 607.1.1. |
| | SHOW THE HOT WATER RECIRCULATION LINE WILL ALSO MAKE |
| | CONNECTION TO THE COLD WATER INLET PIPE OR THE HOT |
| | WATER RETURN CONNECTION OF THE THERMOSTATIC MIXING |
| | VALVE- SEC. 607.2.2 FBC P. PLEASE INCLUDE THE TMV IN |
| | THE EQUIPMENT SCHEDULE ON P001. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |