| 2023-03-09 11:38:22 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-23030381 |
| | 3/9/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P100- IMPORTANT NOTE: SEPARATE PERMITS ARE |
| | REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER AND THE GREASE INTERCEPTOR, AND PERMIT |
| | APPLICATIONS FOR EACH SHALL BE SUBMITTED PRIOR TO |
| | APPROVAL OF THE MAIN PLUMBING PLANS FOR THE PROJECT. |
| | YOU CAN SUBMIT APPLICATIONS TBD (TO BE DETERMINED) IF |
| | YOU DO NOT HAVE CONTRACTORS SELECTED BY EMAILING |
| | COMPLETED PERMIT APPLICATIONS TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) P-100 & P-200: PROVIDE PLUMBING FIXTURE CALCULATIONS |
| | FOR THE NEW BUILDING IN ACCORDANCE WITH TABLE 403.1 FBC |
| | P. PROVIDE SCHEDULES THAT SHOW THE REQUIRED AND |
| | PROVIDED NUMBER OF FIXTURES FOR EACH SEPARATE OCCUPANCY |
| | OR TENANT SPACE. THE CALCULATIONS SHALL CLARIFY WHICH |
| | TENANT SPACES WILL ARE BEING SERVICED BY THE NEW GANG |
| | BATHROOMS, DRINKING FOUNTAINS AND JANITOR???S SINK. |
| | |
| | 3) P-100: SANITARY AND GREASE WASTE STUB UPS ARE NOT |
| | SHOWN IN THE FUTURE TENANT 110 SPACE. IT WOULD APPEAR |
| | AT MINIMUM A SANITARY STUB-UP WOULD BE NECESSARY- SEC. |
| | 107.2.1 WPB. |
| | |
| | 4) P-100: NUMEROUS PLUMBING KEY NOTES REFERENCE THE |
| | CIVIL PLANS WHICH HAVE NOT BEEN UPLOADED FOR REVIEW- |
| | SEC. 107.2.1 WPB. |
| | |
| | 5) P-100: THE FUTURE GREASE INTERCEPTOR PLAN REVIEW |
| | SUBMITTAL SHALL INCLUDE THE FOLLOWING ITEMS. |
| | |
| | A) GREASE WASTE PIPING ISOMETRIC AND A PIPING LAYOUT |
| | PLAN SHOWING PIPE RUNS FROM THE INDIVIDUAL FIXTURES TO |
| | THE MAIN WASTE LINE, WASTE LINE RUN TO THE INTERCEPTOR, |
| | AND OUTLET LINE TO POINT OF CONNECTION TO THE SANITARY |
| | SEWER- SEC. 107.2.1 WPB. |
| | |
| | B) EQUIPMENT SCHEDULE INDICATING THE MAKE, AND MODEL |
| | AND CAPACITY OF THE UNIT- SEC. 1003.3.5. |
| | |
| | C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| | OR PDI G101 FOR HYDROMECHANICAL TYPES- SEC.1003.5.1. |
| | |
| | D) AN ENLARGED PIPING DIAGRAM OR ISOMETRIC SHOWING THE |
| | SIZES OF INLETS, OUTLETS, CLEANOUTS, AND VENTS- SEC. |
| | 107.3.5.1.3 WPB. PLEASE INCLUDE A DETAIL FOR THE |
| | CLEANOUT WHICH WILL BE USED AS THE SAMPLING PORT BY THE |
| | WPB UTILITIES DEPT. |
| | |
| | 6) P-700: THE SANITARY RISER APPEARS TO SHOW IMPROPER |
| | WET-VENTING FOR THE MEN???S AND WOMEN???S BATHROOM |
| | FIXTURES PER ITEMS A-D BELOW. |
| | |
| | A) URINALS ARE NOT INCLUDED IN THE DEFINITION OF A |
| | BATHROOM GROUP SO THEIR FIXTURE DRAINS SHALL NOT |
| | CONNECT TO THE WET VENT, AND THEIR DRY VENTS SHALL NOT |
| | BE THE DRY VENT FOR THE SYSTEM- SECS. 202 & 912.1 FBC |
| | P. IN ORDER TO FIX THE BRANCH, THE URINAL DRAINS SHALL |
| | CONNECT DOWNSTREAM OF THE L2/WC-1 WET VENT, AND A |
| | COMMON VENT OR INDIVIDUAL VENTS FOR THE URINALS SHALL |
| | BE PROVIDED- SECS. 910.1 & 911.1. |
| | |
| | B) THE TWO WET VENT BRANCHES SHOWING 3- WATER CLOSETS |
| | (WC-1) AND 3- LAVATORIES (L-1) ARE NOT IN COMPLIANCE |
| | WITH 912.1 BECAUSE NOT MORE THAN TWO OF ANY FIXTURE |
| | TYPE CAN CONNECT TO A WET-VENT SYSTEM. TO FIX THE |
| | BRANCHES, INDIVIDUAL OR COMMON WC-1 & L-1 VENTS SHALL |
| | BE PROVIDED- SECS. 910.1 & 911. THE L-1 BRANCH CAN ALSO |
| | BE CIRCUIT VENTED IF DESIGNED IN ACCORDANCE WITH SEC. |
| | 914.1- 914.3. |
| | |
| | C) THE BRANCH SHOWING THE 3- LAVATORIES AND THE |
| | JANITOR'S SINK WITH INDIVIDUAL VENT CAN BE FIXED BY |
| | PROVIDING EITHER INDIVIDUAL VENTS OR COMMON VENTS FOR |
| | THE LAVS, OR A CIRCUIT VENT FOR THE WHOLE BRANCH CAN BE |
| | DESIGNED IN ACCORDANCE WITH SECS. 914.1- 914.3 FBC P. |
| | |
| | D) PROVIDE VENTING FOR THE HD AND FD-1- SEC. 901.2.1 |
| | FBC P. PLEASE NOTE THAT BASED ON P-100 THERE APPEARS TO |
| | BE ONE FD-1 MISSING FROM THE ISOMETRIC DRAWING. |
| | |
| | 7) P-700: SHOW TRAP SEAL PROTECTION FOR THE FD-1 AND |
| | HD-1: SEC. 1002.4.1 FBC P. |
| | |
| | 8) P-700 WATER RISER: SHOW THE SIZES OF THE SUPPLY |
| | PIPES TO UR-1 AND WC-1- TABLE 604.5 FBC P. |
| | |
| | 9) P-700: TEMPERED WATER SHALL BE DELIVERED FROM THE |
| | LAVATORIES THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070- SECS. 419.5 & 607.1.2 FBC |
| | P. |
| | |
| | 10) P-700: THE 3/4 -INCH HOT WATER FIXTURE SUPPLY PIPES |
| | TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE |
| | LENGTHS OF 0.5 FT. FROM THE HOT WATER SOURCE TO THE |
| | PIPE TERMINATION. THE NEAREST SOURCE IN THIS CASE IS |
| | THE RECIRCULATION LINE- TABLE C404.5.1 FBC ENERGY. |
| | |
| | 11) P-500: PLEASE PROVIDE A WATER HEATER DETAIL THAT |
| | SHOW THE PIPING CONNECTIONS TO THE RECIRCULATION PUMP, |
| | REQUIRED EXPANSION TANK AND THE REQUIRED MASTER |
| | THERMOSTATIC MIXING VALVE- SECS. 607.2.2 & 607.3 FBC P. |
| | PLEASE NOTE THE MASTER MIXING VALVE IS REQUIRED BECAUSE |
| | THE THERMOSTAT ON THE WATER HEATER CANNOT BE THE |
| | TEMPERATURE LIMITING MEANS FOR THE HOT WATER SYSTEM- |
| | SEC. 607.1.1. |
| | |
| | 12) P-700: PLEASE SHOW THE DRAINAGE GPM'S AT THE ROOF |
| | DRAINS AND THE ACCUMULATIVE GPM FLOW THROUGH THE |
| | VERTICAL LEADERS AND HORIZONAL STORM PIPES TO THE |
| | DISPOSAL LOCATIONS- TABLES 1106.2 & 1106.3 FBC P. |
| | |
| | 13) A104 & A104A: PLEASE PROVIDE THE FOLLOWING FBC ACC |
| | COMPLIANCE DETAILS FOR THE ACCESSIBLE BATHROOM FIXTURES |
| | AND DRINKING FOUNTAINS. PLEASE NOTE KEYNOTES 1-4 NOT |
| | SHOWN ON THE DRAWINGS. |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | AND PARTITIONS- SEC. 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | F) HEIGHTS OF THE ACCESSIBLE COMPARTMENT LAVATORY SINK |
| | RIMS FROM THE FINISHED FLOORS- SEC. 606.3. |
| | G) HEIGHTS OF THE ACCESSIBLE COMPARTMENT MIRRORS FROM |
| | THE FINISHED FLOORS TO THE REFLECTIVE SURFACES- SECTION |
| | 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 604.5.2. |
| | I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| | 604.7. |
| | J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2. |
| | K) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND |
| | PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH |
| | TO THE FOUNTAIN- SEC. 602.2 FBC ACC, AND SHOW HOW THE |
| | LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH |
| | SEC. 307.2 PROTRUSION LIMITS. IT APPEARS ONE SIDE OF |
| | THE FOUNTAIN IS BEYOND THE 4-INCH MAXIMUM PROTRUSION |
| | LIMITATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |