| 2023-03-10 06:16:17 | 1ST REVIEW FMC |
| | PERMIT: 23030381 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT. |
| | FEC C402.1 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | FOR THIS PROJECT. FEC C403.2.1 |
| | |
| | 3) SHOW THAT ALL ROOFTOP EQUIPMENT WILL HAVE THE |
| | REQUIRED CLEARANCE FROM THE ROOFS EDGE OR PROVIDE |
| | GUARDS. FMC 304.11 |
| | |
| | 4) THE LIFE SAFETY SHEET INDICATES RATED WALLS. SHOW |
| | HOW THE PENETRATIONS MADE BY THE MECHANICAL DUCTWORK |
| | WILL BE PROTECTED. FMC 607.5.2 |
| | |
| | 5) PROVIDE DUCT SMOKE DETECTORS IN ALL MECHANICAL |
| | SYSTEMS THAT MEET THE REQUIREMENTS OF FMC 606.2 |
| | |
| | 6) PROVIDE A SPEC SHEET FOR THE MECHANICAL EQUIPMENT |
| | SHOWN ON THE MECHANICAL DRAWINGS. FBC 107.3.5 |
| | |
| | 7) ADD A NOTE ON THE MECHANICAL DRAWINGS STATING THAT |
| | THE DUCTWORK FOR FUTURE USE MAY BE REVISED AT TENANT |
| | UPFIT. |
| | |
| | 8) SHOW THAT ALL EXHAUST TERMINATIONS MEET THE DISTANCE |
| | REQUIREMENTS OF FMC 501.3 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |