| Plan Review Notes For Permit 23030379 |
| Permit Number |
23030379 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-10 09:23:17 | LIGHT POLES | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) AS NOTED ON DRAWING E101 - NEED A SIGNED AND SEALED | | | DRAWING THAT INCLUDES THE ENTIRE ASSEMBLY (POLE AND | | | FIXTURE) - PLEASE PROVIDE SIGNED AND SEALED LIGHT POLE | | | DRAWINGS SHOWING THE WIND DESIGN PARAMETERS FROM A | | | DESIGN PROFESSIONAL AS NOTED ON THE PROVIDED DRAWINGS. | | | FBC 1609 | | | | | | 2) POLE DRAWING FROM "VALMONT" DOES NOT INCLUDE THE | | | LIGHT FIXTURE. POLE LENGTH AND EMBEDMENT DEPTH DOES NOT | | | MATCH DRAWING E101 AND IT IS NOT SIGNED AND SEALED BY | | | THE DESIGNER. FBC WPB 107.1 | | | |
|