| 2023-03-09 13:54:42 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | NOTE #2 CALLS FOR CCTV SYSTEM INSIDE OR OUTSIDE OF | | | POLE? SEE BELOW. EXPLAIN HOW WIRING IS TO BE DONE. | | | | | | CABLES AND CONDUCTORS OF CLASS 2 AND CLASS 3 CIRCUITS | | | SHALL NOT BE PLACED IN ANY CABLE, CABLE TRAY, | | | COMPARTMENT, ENCLOSURE, MANHOLE, OUTLET BOX, DEVICE | | | BOX, RACEWAY, OR SIMILAR FITTING WITH CONDUCTORS OF | | | ELECTRIC LIGHT, POWER, CLASS 1, NON???POWER-LIMITED | | | FIRE ALARM CIRCUITS, AND MEDIUM-POWER NETWORK-POWERED | | | BROADBAND COMMUNICATIONS CIRCUITS UNLESS PERMITTED BY | | | 725.136(B) THROUGH (I). |
|