 NOTE #2 CALLS FOR CCTV SYSTEM INSIDE OR OUTSIDE OF
 POLE? SEE BELOW. EXPLAIN HOW WIRING IS TO BE DONE.
  
 CABLES AND CONDUCTORS OF CLASS 2 AND CLASS 3 CIRCUITS
 SHALL NOT BE PLACED IN ANY CABLE, CABLE TRAY,
 COMPARTMENT, ENCLOSURE, MANHOLE, OUTLET BOX, DEVICE
 BOX, RACEWAY, OR SIMILAR FITTING WITH CONDUCTORS OF
 ELECTRIC LIGHT, POWER, CLASS 1, NON???POWER-LIMITED
 FIRE ALARM CIRCUITS, AND MEDIUM-POWER NETWORK-POWERED
 BROADBAND COMMUNICATIONS CIRCUITS UNLESS PERMITTED BY
 725.136(B) THROUGH (I).