Plan Review Notes
Plan Review Notes For Permit 23030366
Permit Number 23030366
Review Stop Z
Sequence Number 1
Notes
Date Text
2023-04-11 14:29:22FAILED
  
 THE CITYPLACE DEVELOPMENT REGULATIONS REQUIRE THE
 SCREENING OF ROOFTOP MECHANICAL EQUIPMENT. PROVIDE THE
 HEIGHT OF THE GENERATOR PLUS THE MOUNTING RACK FROM THE
 ROOF DECK AND THE HEIGHT OF THE PARAPET WALL FROM THE
 ROOF DECK TO VERIFY THAT THE PARAPET HEIGHT EXCEEDS THE
 HEIGHT OF THE TOP OF THE GENERATOR. .WHILE SHEET A-5
 APPEARS TO SHOW THE PARAPET EXCEEDING THE GENERATOR,
 PLEASE PROVIDE THE DIMENSIONS.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]