Plan Review Notes
Plan Review Notes For Permit 23030366
Permit Number 23030366
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-24 14:32:47ROOF TOP GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE HEIGHT OF THE PARAPET WALL - FBC
 1015.6 MECHANICAL EQUIPMENT, SYSTEMS AND DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
  