| 2023-03-13 12:39:43 | 1ST REVIEW FMC | | | PERMIT: 23030346 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A SCOPE OF WORK FOR THE MECHANICAL SYSTEM. | | | IS THE SYSTEM BEING REPLACED? IS THE DUCTWORK BEING | | | REPLACED? | | | | | | 2) SHOW THE RETURN AIR PATH FROM THE ROOMS BACK TO THE | | | MECHANICAL SYSTEM. FMC 601.6 | | | | | | 3) IS THE KITCHEN HOOD DUCTED TO THE EXTERIOR? WHAT ARE | | | THE CFMS OF THE HOOD EXHAUST FAN? IF OVER 400 CFM | | | PROVIDE THE MAKE-UP AIR FOR THIS HOOD. FMC 505.2 | | | | | | 4) THE DESIGNER MUST DIGITALLY SIGN DIGITALLY SUBMITTED | | | DOCUMENTS. FS 471/481 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|