| 2023-04-10 14:28:06 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL41940 |
| | COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED |
| | ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2 |
| | MECHANICALLY-ATTACHED BASE SHEET TABLE 4B ALLOWABLE |
| | DESIGN PRESSURES, 2-PLY UNDERLAYMENT SYSTEMS IN TILE |
| | ROOF APPLICATIONS SYSTEM NO. UDL-12 DO NOT MEET OR |
| | EXCEED THE MINIMUM DESIGN PRESSURE REQUIREMENTS FOR A |
| | HIP ROOF; (3:12 AND OVER) ROOF SLOPE; MEAN ROOF HEIGHT |
| | 15 FT. MINIMUM DESIGN PRESSURE REQUIREMENT OF -115.5 IN |
| | AN EXPOSURE CATEGORY C AREA. PROVIDE UNDERLAYMENT |
| | SYSTEM THAT MEETS OR EXCEEDS THE ABOVE CRITERIA. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |