Plan Review Notes
Plan Review Notes For Permit 23030340
Permit Number 23030340
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-27 10:31:15JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL2346-R8 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT). TEST REPORT PAGES 1-3.
 INSTALLATION INSTRUCTIONS PAGES 1 & 2. THE TEST REPORTS
 AND INSTALLATION INSTRUCTIONS CAN BE PRINTED FROM THE
 SUMMARY OF PRODUCTS LOCATED AT THE BOTTOM OF THE COVER
 PAGE.
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5374-R6 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL4190 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS
 WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER,
 STATUS, GENERAL INFORMATION ABOUT THE PRODUCT).
 4. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL41940
 (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF
 WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT
 CONSIDER USING FL41940 (NON-HVHZ).
 5. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL41940
 (NON- HVHZ) COVERS MULTIPLE PRODUCT TYPES; ROOF COVER
 OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES, ATTACHMENT
 LIMITATIONS & INSTALLATION APPROVED ASSEMBLIES. SELECT
 ALL APPLICABLE OPTIONS INCLUDING ATTACHMENT LIMITATION
 SYSTEM USED FROM 5.8.3.1 DIRECT-TO-DECK TABLE 4A:
 ALLOWABLE DESIGN PRESSURES, DIRECT-TO-DECK UNDERLAYMENT
 IN TILE ROOF APPLICATIONS PAGE #4 & 5 OR ATTACHMENT
 LIMITATION SYSTEM FROM 5.8.3.2 MECHANICALLY-ATTACHED
 BASE SHEET TABLE 4B ALLOWABLE DESIGN PRESSURES, 2-PLY
 UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS PAGES
 #6-9.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  