Plan Review Notes
Plan Review Notes For Permit 23030322
Permit Number 23030322
Review Stop E
Sequence Number 2
Notes
Date Text
2023-04-19 16:29:12ELECTRIC REVIEW FAILED
  
 1) OVERCURRENT PROTECTION DETAILED FOR FEEDER TO MDP2
 ARE REQUIRED TO BE RATED AT 125% OF THE CONTINUOUS
 LOAD, (915 X 1.25%= 1144 AMPERES) IN ACCORDANCE WITH
 NEC 215.3. THE RATING OF THIS DEVICE IS REQUIRED TO BE
 A MINIMUM RATING OF 1200 AMPS IN ACCORDANCE WITH THE
 STANDARD AMPERE RATINGS LISTED IN NEC 240.6(A). PLEASE
 CORRECT FEEDER OVERCURRENT PROTECTION SIZE AS
 APPLICABLE.
  
 2) FEEDER CONDUCTORS DETAILED FROM FPL TRANSFORMER TO
 MDS2 AND MDS2 TO MDP2 ARE DETAILED AS (3) SETS OF
 400MCM CONDUCTORS WITH A TOTAL AMPACITY OF 1005 AMPS.
 THE INDUSTRIAL PROCESS GLASS TEMPERING HEATER ARE
 REQUIRED TO BE CONSIDERED A CONTINUOUS LOAD IN
 ACCORDANCE WITH NEC 424.3(B). CONDUCTORS SUPPLYING
 CONTINUOUS LOADS IS REQUIRED TO BE RATED AT 125% OF THE
 LOAD SERVED IN ACCORDANCE WITH NEC 215.2(A)(1)(A). THE
 TOTAL LOAD FOR THE GLASS TEMPERING HEATER IS DETAILED
 AS 915 AMPS. MINIMUM CONDUCTOR AMPACITY REQUIRED IS 915
 X 1.25=1144 AMPS. NEC 424.3(B) NEC 215.2(A)(1)(A).
 IN ADDITION, ENSURE THE CONDUCTOR AMPACITY RATING IS
 EQUAL OR GREATER THAN THE OVERCURRENT DEVICE PROTECTING
 WITH A RATING OVER 800 AMPERES, IN ACCORDANCE WITH NEC
 240.4(C). PLEASE CORRECT FEEDER CONDUCTOR SIZE AS
 APPLICABLE.
  
 3) OVERCURRENT PROTECTION DETAILED AS 500 AMPERES FOR
 BRANCH CIRCUIT CONDUCTORS TO GLASS HEATERS 1 AND 2 ARE
 REQUIRED TO BE RATED AT 125% OF THE CONTINUOUS LOAD,
 (349 X 1.25%= 436 AMPERES) IN ACCORDANCE WITH NEC
 210.20(A)THE RATING OF THIS DEVICE IS REQUIRED TO BE A
 MINIMUM RATING OF 450 AMPS IN ACCORDANCE WITH THE
 STANDARD AMPERE RATINGS LISTED IN NEC 240.6(A) AND A
 MAXIMUM RATING OF 450 AMPERES IN ACCORDANCE WITH NEC
 670.4(C). PLEASE CORRECT BRANCH CIRCUIT OVERCURRENT
 PROTECTION SIZE AS APPLICABLE.
  
 4) BRANCH CIRCUIT CONDUCTORS DETAILED AS 500MCM TO
 GLASS HEATERS 1 AND 2 WITH AN AMPACITY OF 380 AMPERES.
 THE INDUSTRIAL PROCESS GLASS TEMPERING HEATERS 1 AND 2
 ARE REQUIRED TO BE CONSIDERED A CONTINUOUS LOAD IN
 ACCORDANCE WITH NEC 424.3(B). CONDUCTORS SUPPLYING
 CONTINUOUS LOADS IS REQUIRED TO BE RATED AT 125% OF THE
 LOAD SERVED IN ACCORDANCE WITH NEC 21O.19(A)(1)(A). THE
 TOTAL LOAD FOR EACH GLASS TEMPERING HEATER IS DETAILED
 AS 349 AMPS. MINIMUM CONDUCTOR AMPACITY REQUIRED IS 349
 X 1.25=436 AMPERES. PLEASE CORRECT BRANCH CIRCUIT
 CONDUCTOR SIZE AS APPLICABLE.
  
 5) BRANCH CIRCUIT CONDUCTORS DETAILED AS 4/0. THE
 LISTED ALLOWED AMPACITY OF 4/0 IS 230 AMPERES. THE
 BLOWER MOTOR IS REQUIRED TO BE CONSIDERED A CONTINUOUS
 LOAD IN ACCORDANCE WITH NEC 670.4(A). CONDUCTORS
 SUPPLYING CONTINUOUS LOADS ARE REQUIRED TO BE RATED AT
 125% OF THE LOAD SERVED IN ACCORDANCE WITH NEC
 670.4(A). THE TOTAL LOAD FOR THIS MOTOR IS DETAILED AS
 224 AMPERES. MINIMUM CONDUCTOR AMPACITY REQUIRED IS 224
 X 1.25=280 AMPERES. PLEASE CORRECT BRANCH CIRCUIT
 CONDUCTOR SIZE AS APPLICABLE.
  
 6) THE PANEL SCHEDULE FOR MDP2 LISTS THE CONTROL
 CIRCUIT AS HAVING A 100 AMPERE CIRCUIT BREAKER. THE
 CONDUCTOR SIZE IS LISTED AS A #8 CONDUCTOR. PLEASE
 CORRECT THE OVERCURRENT PROTECTION SIZE IN ACCORDANCE
 WITH NEC 240 REQUIREMENTS. PLEASE NOTE: SUBMITTAL OF
 ADDITIONAL AND/OR REVISED MATERIALS MAY RESULT IN NEW
 PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
 7) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACT OR,
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  