| Date |
Text |
| 2023-03-09 16:25:56 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | NEED SPECS ON EQUIPMENT BEING INSTALLED, GAS FIRED?, |
| | ELECTRIC? EXHAUST SYSTEM? SPRINKLER SYSTEM REQUIRED? |
| | |
| | PLANS NEED TO BE SIGNED AND SEALED BY AN ENGINEER |
| | |
| | |
| | WHERE A BUILDING OR STRUCTURE IS SUPPLIED BY MORE THAN |
| | ONE SERVICE, OR ANY COMBINATION OF BRANCH CIRCUITS, |
| | FEEDERS, AND SERVICES, A PERMANENT PLAQUE OR DIRECTORY |
| | SHALL BE INSTALLED AT EACH SERVICE DISCONNECT LOCATION |
| | DENOTING ALL OTHER SERVICES |
| | |
| | F.S. 471.003 (H)???ANY ELECTRICAL, PLUMBING, |
| | AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE |
| | PRACTICE INCLUDES THE DESIGN AND FABRICATION OF |
| | ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR MECHANICAL |
| | SYSTEMS, RESPECTIVELY, WHICH SHE OR HE INSTALLS BY |
| | VIRTUE OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER |
| | 1PART I OF CHAPTER 553, OR UNDER ANY SPECIAL ACT OR |
| | ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT |
| | WHICH: |
| | |
| | 1.???REQUIRES AN ELECTRICAL OR PLUMBING OR |
| | AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE |
| | OF $125,000 OR LESS; AND |
| | |
| | 2.A .REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 |
| | AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL |
| | SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A |
| | COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM; |
| | |
| | |