Plan Review Notes
Plan Review Notes For Permit 23030322
Permit Number 23030322
Review Stop E
Sequence Number 1
Notes
Date Text
2023-03-09 16:25:56FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED SPECS ON EQUIPMENT BEING INSTALLED, GAS FIRED?,
 ELECTRIC? EXHAUST SYSTEM? SPRINKLER SYSTEM REQUIRED?
  
 PLANS NEED TO BE SIGNED AND SEALED BY AN ENGINEER
  
  
 WHERE A BUILDING OR STRUCTURE IS SUPPLIED BY MORE THAN
 ONE SERVICE, OR ANY COMBINATION OF BRANCH CIRCUITS,
 FEEDERS, AND SERVICES, A PERMANENT PLAQUE OR DIRECTORY
 SHALL BE INSTALLED AT EACH SERVICE DISCONNECT LOCATION
 DENOTING ALL OTHER SERVICES
  
 F.S. 471.003 (H)???ANY ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL CONTRACTOR WHOSE
 PRACTICE INCLUDES THE DESIGN AND FABRICATION OF
 ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR MECHANICAL
 SYSTEMS, RESPECTIVELY, WHICH SHE OR HE INSTALLS BY
 VIRTUE OF A LICENSE ISSUED UNDER CHAPTER 489, UNDER
 1PART I OF CHAPTER 553, OR UNDER ANY SPECIAL ACT OR
 ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT
 WHICH:
  
 1.???REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
  
 2.A .REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM;
  
  