2023-06-13 12:53:491ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23030263
 6/12/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES.
  
 2) P-3 & P-6: A VENT IS REQUIRED FOR P-1 WATER CLOSET
 IN THE MEN'S RESTROOM- SEC. 901.2.1 FBC P.
  
 3) P-2 & P-6: PLEASE SHOW THE MEANS OF PROVIDED
 TEMPERED WATER DELIVERY FROM THE PUBLIC LAVATORIES-
 SEC. 419.5 & 607.1.2 FBC P.
  
 4) P-2 & P-6: THE LENGTH OF THE HOT WATER SUPPLY PIPES
 TO THE PUBLIC LAVATORIES IS EXCEEDING THE MAXIMUM 2 FT.
 ALLOWABLE DISTANCE BASED ON TABLE C404.5.1 FBC ENERGY
 CONSERVATION. TO BE CODE COMPLIANT THE POINT OF USE
 WATER HEATERS SHALL BE RELOCATED TO POINTS WITHIN RANGE
 OR PROVIDE RECIRCULATION PUMPS FOR THE SYSTEM.
  
 5) A-402 & A-403: BASED ON THE NOTES ON SHEET AG-101
 WHICH INDICATES DEMOLITION OF EXISTING INTERIOR
 PARTITIONS, THE MEN'S AND WOMEN'S RESTROOMS ARE NEW
 CONSTRUCTION AND SHALL BE DESIGNED AND CONSTRUCTED WITH
 LAVATORIES INSIDE THE WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENTS- SEC. 604.8.1.6 FBC ACC & FL. STATUTE
 553.504. PLEASE REVISE THE PLANS ACCORDINGLY.
  
 6) A-402: CORRECT THE DETAILS SHOWING THE CENTERLINES
 OF THE WATER CLOSETS AS 1'-3" MEASURED FROM THE
 ADJACENT WALLS- SEC. 604.2 FBC ACC.
  
 7) A-401, A-402, & A-403: SHOW THE WATER CLOSET GRAB
 BAR LENGTHS AND HEIGHTS AS SHOWN IN SECS. & FIGURES
 604.5.1 & 604.5.2, AND SEC. 609.4 FBC ACC. THE CURRENT
 DETAIL FOR THE REAR BAR DOES NOT SHOW THE MINIMUM
 24-INCH EXTENSION FROM THE CENTERLINE OF THE TOILET TO
 THE OPEN SIDE AND DOES NOT SHOW THE HEIGHTS MEASURED TO
 THE TOPS OF THE GRIPPING SURFACES.
  
 8) A-401, A-402, & A-403: SHOW THE ACCESSIBLE LAVATORY
 KNEE AND TOES CLEARANCES AS SHOWN IN THE FIGURES 306.2
 & 306.3 FBC ACC.
  
 9) A-401, A-402, & A-403: SHOW THE CENTERLINES OF THE
 TOILET PAPER DISPENSERS TO BE 7-INCHES AND 9-INCHES
 MAXIMUM MEASURED FROM THE FRONTS OF THE WATER CLOSETS-
 SEC. AND FIGURE 604.7.
  
 10) A-404: THE EXECUTIVE BATHROOM DESIGN WILL NOT MEET
 COMPLIANCE WITH SECS. 213.2, 603.1, 603.2.2, & 608.2.1
 FBC ACC BECAUSE THE REQUIRED CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS FOR THE FIXTURES HAVE NOT BEEN PROVIDED.
 PLEASE NOTE THAT FULL FIXTURE ACCESSIBILITY COMPLIANCE
 IS NOT REQUIRED FOR THE PRIVATE BATHROOMS HOWEVER CLEAR
 FLOOR SPACES FOR FIXTURES AND GRAB BAR BACKINGS SHALL
 BE PROVIDED. PLEASE REVIEW THE FOLLOWING CODE SECTIONS
 AND CORRECT THE PLANS- 604.3, 604.5 EXCEPTION 1, 604.7,
 606.2 EXCEPTION 2, 606.3 EXCEPTION 1, 608.2.1, & 608.3.
  
 11) ADDITIONAL FBC ACC COMPLIANCE DETAILS REQUIRED:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS AND KNEE
 AND TOE CLEARANCES FOR THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN- 602.2.
 B) SPOUT HEIGHTS OF THE WHEELCHAIR ACCESSIBLE FOUNTAIN
 AND STANDING PERSON'S FOUNTAIN- 602.4- 602.7.
 C) BREAKROOM SINKS- CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS, SINK HEIGHTS AND KNEE AND TOE CLEARANCES-
 606.2 & 606.3.
  
 11) P-4: PLEASE CORRECT NOTE 1 INDICATING EXISTING ROOF
 DRAINAGE TO REMAIN. BASED ON THE ARCHITECTURAL AND
 STRUCTURAL PLANS A COMPLETE NEW STRUCTURAL ROOF SYSTEM
 WILL BE INSTALLED. PROVIDE COMPLETE ROOF DRAINAGE PLANS
 IN ACCORDANCE WITH SECS. 1105, 1106, & 1108 FBC P.
 PLEASE PROVIDE THE FOLLOWING-
 A) LOCATIONS AND SIZES OF PRIMARY AND SECONDARY DRAINS,
 AND THE SIZES OF PRIMARY AND SECONDARY HORIZONTAL AND
 VERTICAL ROOF DRAIN PIPES.
 B) RAINFALL RATE AND ROOF SQ. FT. AREA AND GPM FLOW
 CALCULATIONS INCLUDING PARAPET WALLS.
 C) ISOMETRIC DRAWING SHOWING THE PRIMARY AND SECONDARY
 PIPE RUNS AND SIZES, TERMINATION AND CLEANOUT
 LOCATIONS.
 D) ROOF DRAIN INSTALLATION DETAIL, AND SCUPPER DETAIL
 (IF APPLICABLE).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  