| 2023-05-18 10:58:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE PLAN SHEET SUBMITTALS APPEAR TO BE INCOMPLETE AS |
| | THERE IS NO FLOOR PLAN SHOWING THE LOCATION OF WALLS, |
| | RESTROOMS, OFFICES, CONFERENCE ROOMS, ETC. |
| | |
| | THERE ARE INDICATIONS OF ENLARGED RESTOOMS AND |
| | CONFERENCE ROOM BUT NO PLOOR PLAN |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW AND PROVIDE A FLOOR DETAILED PLAN. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF AN ELECTICAL PLAN |
| | INCLUDING EXIT OR EMERGENCY LIGHTING. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAILED ELECTRICAL PLAN. |
| | |
| | |
| | 3) THERE IS NO INDICATION OF A MECHANICAL A/C PLAN. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAILED MECHANICAL PLAN. |
| | |
| | |
| | 4) DUE TO THE ABOVE NOTED COMMENTS, PLEASE PROVIDE A |
| | LIFE SAFETY PLAN INCLUDING TRAVEL PATHS AND DISTANCES |
| | IN COMPLAINAE WITH THE APPLICABLE NFPA 101 OCCUPANCY |
| | REQUIRMENTS. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |