Plan Review Notes
Plan Review Notes For Permit 23030263
Permit Number 23030263
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-18 10:58:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PLAN SHEET SUBMITTALS APPEAR TO BE INCOMPLETE AS
 THERE IS NO FLOOR PLAN SHOWING THE LOCATION OF WALLS,
 RESTROOMS, OFFICES, CONFERENCE ROOMS, ETC.
  
 THERE ARE INDICATIONS OF ENLARGED RESTOOMS AND
 CONFERENCE ROOM BUT NO PLOOR PLAN
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND PROVIDE A FLOOR DETAILED PLAN.
  
  
 2) THERE IS NO INDICATION OF AN ELECTICAL PLAN
 INCLUDING EXIT OR EMERGENCY LIGHTING.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND PROVIDE A DETAILED ELECTRICAL PLAN.
  
  
 3) THERE IS NO INDICATION OF A MECHANICAL A/C PLAN.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND PROVIDE A DETAILED MECHANICAL PLAN.
  
  
 4) DUE TO THE ABOVE NOTED COMMENTS, PLEASE PROVIDE A
 LIFE SAFETY PLAN INCLUDING TRAVEL PATHS AND DISTANCES
 IN COMPLAINAE WITH THE APPLICABLE NFPA 101 OCCUPANCY
 REQUIRMENTS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  