| Plan Review Notes For Permit 23030237 |
| Permit Number |
23030237 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-22 11:37:06 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER DIAGRAM SEEMS INCOMPLETE PLEASE SUBMIT AN | | | EXISTING RISER DIAGRAM AND A NEW RISER DIAGRAM. | | | | | | TESLA BACKUP GATEWAY DOES IT HAVE BREAKERS INSIDE TO | | | REDUCE OVERCURRENT PROTECTION TO THE 200A PANEL, AND | | | 150 TO SOLAR DISCONNECT WITH 1/0S? | | | | | | GATEWAY IS RATED FOR 200A YOU NEED 200A WIRE. 3/0 | | | | | | PANEL A DOES NOT SEEM TO BE THE ONLY PANEL SO 2/0 | | | CONDUCTORS WILL NEED TO BE REPLACED WITH 3/0S. | | | | | | 200A BREAKER OFF THE BUSS PLEASE SUBMIT THE BUSS | | | CALCULATION. | | | | | | PLEASE SUBMIT A COST BREAKDOWN TFOR THE ENTIRE SYSTEM | | | WITH ALL MATERIALS AND LABOR. |
|