| Plan Review Notes For Permit 23030205 |
| Permit Number |
23030205 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-10 16:28:26 | 1ST REVIEW FMC | | | PERMIT: 23030205 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: KEYNOTE 1 IS CALLING FOR MAKE-UP AIR FOR | | | THE KITCHEN HOOD. SHOW THIS DUCT WORK AND TERMINATION | | | LOCATION ON THE DRAWING. FRC M1503.4 | | | | | | 2) SHEET M-1: THE MODIFIED DAYROOM HAS POCKET DOORS. | | | PROVIDE THE RETURN AIR PATH FROM THE DAYROOM BACK TO | | | THE RETURN IN THE LIVING ROOM WHEN THE DOORS ARE | | | CLOSED. FRC M1602.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|