2023-04-17 11:56:08FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 2. AT LEAST ONE 120-VOLT, 20-AMPERE BRANCH CIRCUIT
 SHALL BE INSTALLED TO SUPPLY RECEPTACLE OUTLETS IN
 ATTACHED GARAGES AND IN DETACHED GARAGES WITH ELECTRIC
 POWER. THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS AS PER
 NEC 210.11(C)(4)
  
 3. INFORMATION PROVIDED ON PAGE 018 E1 ELECTRICAL PLAN
 (ELECTRICAL RISER DIAGRAM) DOES NOT MATCH THE
 INFORMATION ON PAGE 019 UE1 UNIT ELECTRICAL (ELECTRICAL
 RISER).
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  