| 2023-03-01 09:58:48 | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 23021469 | | | 3/1/2023 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.0: REVISE THE COMBUSTION AIR CALCULATIONS | | | TO INCLUDE THE RANGE IN THE KITCHEN- SEC. G2407.1 FBC | | | RES. IF USING THE STANDARD INDOOR AIR METHOD, THE RANGE | | | IN THE KITCHEN WILL REQUIRE 5000 CU. FT., AND THE | | | FIREPLACE IN THE GREAT ROOM WILL REQUIRE 2000 CU. FT. | | | PLEASE NOTE THE CODE ALLOWS FOR ALL OPEN AREAS BY THE | | | GREAT ROOM AND KITCHEN TO BE USED INCLUDING THE ENTRY | | | FOYER, STAIRWAY, HALLWAY, AND OFFICE. | | | | | | A) PLEASE CORRECT THE CALCULATIONS FOR THE FIREPLACE IN | | | LIVING ROOM 09 THAT SPECIFY KITCHEN AT 2240 ROOM | | | VOLUME. PLEASE NOTE 2000 CU. FT. IS REQUIRED THEREFORE | | | THE 2240 PROVIDED IN THE LIVING ROOM IS ADEQUATE. | | | B) PLEASE CORRECT THE CALCULATIONS FOR THE FIREPLACE IN | | | THE GREAT ROOM- SEE COMMENT #1 ABOVE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|