| 2023-02-28 07:05:13 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021456 |
| | 2/28/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: IN ORDER TO HELP EXPEDITE THE REVIEW OF |
| | THE GAS PIPING SYSTEM, PLEASE IDENTIFY THE TYPE OF PIPE |
| | AT EACH SECTION OR BRANCH SHOWN IN THE RISER, AND |
| | PROVIDE A SEPARATE FLOOR PLAN DRAWING THAT THAT SHOWS |
| | THE EXTERIOR AND INTERIOR GAS PIPING RUNS AND APPLIANCE |
| | LOCATIONS- SEC. 107.2.1 WPB AND SEC. G2413.1 FBC RES. |
| | A) FLOOR PLAN DRAWING: PLEASE SHOW THE LOCATIONS AND |
| | TERMINATION POINTS OF ALL SLEEVES AND CONDUITS INTERIOR |
| | AND EXTERIOR OF THE BUILDING AND HOW THE OPEN ENDS WILL |
| | BE SEALED AND VENTED WHERE REQUIRED- SEE SECS. |
| | G2415.14.1- G2415.14.2 FBC RES. |
| | |
| | 2) P1: PE PIPING IS RATED AND LABELED FOR DIRECT |
| | UNDERGROUND BURIAL AND DOES NOT REQUIRE A PVC CONDUIT |
| | OR SLEEVE. PLEASE CORRECT THE NOTE ON THE DRAWING, AND |
| | NOTE THAT PE PIPING SHALL NOT BE INSTALLED UNDER THE |
| | BUILDING WHETHER SLEEVED OR NOT AND REQUIRES |
| | INSTALLATION OF A TRACER WIRE- SEE SECS. G2417.1- |
| | G2417.3 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |