| 2023-03-13 17:31:12 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 23021437 |
| | 3/13/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P2: PLEASE PROVIDE A COMPLETE GAS RISER |
| | DRAWING FOR THE PROJECT THAT SHOWS THE CONTINUOUS |
| | PIPING RUN FROM THE METER TO THE MOST REMOTE OUTLET. |
| | PLEASE INCLUDE ALL EXITING GAS PIPING AND EXISTING GAS |
| | APPLIANCES ALONG WITH THE NEW INSTALLATIONS- SEC. |
| | G2412.3, G2412.4, & G2413.4.1 FBC RES. THE CURRENT |
| | RISER AND PLAN IS CONFUSING BECAUSE IT APPEARS TO SHOW |
| | TWO DIFFERENT SYSTEMS- ONE FOR THE WATER HEATER AND ONE |
| | FOR THE RANGE. |
| | |
| | A) P2: THE GAS NOTES INDICATE A TOTAL LOAD OF 199,000 |
| | WHICH IS ONLY THE WATER HEATER. PLEASE INCLUDE THE |
| | LOADS OF ALL EXISTING GAS APPLIANCES AT THE RESIDENCE- |
| | SEE COMMENT #1 ABOVE. |
| | |
| | 2) P2: PLEASE SHOW THE CLEARANCE DISTANCE FROM THE |
| | TANKLESS WATER HEATER EXHAUST TO THE WINDOW IN THE |
| | HALLWAY. PLEASE NOTE A MINIMUM 4 FT. CLEARANCE IS |
| | REQUIRED TO OPERABLE OPENINGS- SECS. G2427.8 & G2448.1 |
| | FBC RES. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE- |
| | SEC. G2407.1 FBC RES. PLEASE NOT IF USING THE STANDARD |
| | METHOD OF INDOOR AIR VOLUME, A MINIMUM OF 6000 CU. FT. |
| | IS REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |