| 2023-03-15 09:03:01 | 1ST REVIEW FMC |
| | PERMIT: |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHOW ON THE MECHANICAL DRAWING THE RETURN AIR PATH |
| | FROM THE DESIGN STUDIO TO EXISTING RTU-1 WHEN THE DOORS |
| | ARE CLOSED. FMC 601.6 |
| | |
| | 2) WHAT WAS THE PREVIOUS OCCUPANCY OF THIS SPACE? IT |
| | APPEARS THAT IT WAS STORAGE. IF SO PROVIDE THE REQUIRED |
| | CHANGE OF USE APPLICATION. IF IT IS A CHANGE OF USE |
| | FROM STORAGE TO MERCANTILE PROVIDE THE ENERGY |
| | CALCULATIONS AND MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THIS NEW OCCUPANCY. THE EXISTING RTUS |
| | WOULD NOT HAVE BEEN SIZED ON A SHELL PERMIT AS THE USE |
| | OF SPACE WOULD HAVE BEEN KNOW. FEBC 301.3 |
| | |
| | 3) THE MECHANICAL DRAWING SPECIFIES 3 EXISTING RTUS BUT |
| | THE AERIAL VIEW DOES NOT SHOW RTUS ON THE ROOF OF THIS |
| | BUILDING. PLEASE EXPLAIN. FBC 107.3.5 |
| | |
| | 4) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE |
| | OCCUPANCY CLASSIFICATION FROM TABLE 403.3.1.1 THAT MOST |
| | CLOSELY RESEMBLES EACH USE OF SPACE IN THIS NEW TENANT |
| | SPACE. IT APPEARS THAT THIS SPACE HAS OFFICES, A LOBBY, |
| | CONFERENCE ROOMS. FMC 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |