| 2023-03-07 09:56:10 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23021403 |
| | 3/7/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-1: BASED ON THE PLANS IT APPEARS THE SCOPE |
| | OF PLUMBING WORK IS TO REPLACE THE WATER HEATER, THE |
| | RESTROOM FIXTURES, AND INSTALL A NEW HOSE BIB. PLEASE |
| | CONFIRM AND PROVIDE NOTES OR DETAILS ON THE PLAN |
| | SPECIFYING ACCESSIBLE WATER CLOSETS AND LAVATORIES WILL |
| | BE INSTALLED- SECS. (213.1- 213.3.4), (604.1- 604.4), & |
| | (606.1- 606.5) FBC ACC. |
| | |
| | 2) P-1: THE SANITARY RISER SHOWS EXISTING DRAIN AND |
| | VENT PIPING HOWEVER PLEASE NOTE THE FIXTURE DRAIN FOR |
| | THE DRINKING FOUNTAINS SHOULD NOT BE CONNECTING TO THE |
| | WET VENT FOR THE BATHROOM FIXTURES, AND SHOULD BE |
| | MAKING CONNECTION DOWNSTREAM OF THE VENT- SEC. 912.1 |
| | FBC P. |
| | |
| | 3) P-1: THE WATER HEATER DETAIL SHOWS A MOP SINK BELOW |
| | THE UNIT HOWEVER NO PIPING FOR THE FIXTURE IS SHOWN IN |
| | THE RISER DRAWINGS. PLEASE NOTE THE MOP SINK IS A |
| | REQUIRED FIXTURE FOR STORAGE OCCUPANCIES- TABLE 403.1 |
| | FBC P. |
| | |
| | 4) P-1: A MEANS OF LIMITING THE HOT WATER TEMPERATURE |
| | DELIVERY OTHER THAN THE WATER HEATER THERMOSTAT IS |
| | REQUIRED. PLEASE PROVIDE A MASTER THERMOSTATIC MIXING |
| | VALVE AND REVISE THE WATER HEATER DETAIL TO SHOW THE |
| | LOCATION OF THE DEVICE AND PIPING CONNECTIONS- SEC. |
| | 607.1.1 FBC P. |
| | |
| | 5) P-1: TEMPERED WATER SHALL BE DELIVERED FROM THE |
| | LAVATORIES THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070- SECS. 419.5 & 607.1.2 FBC |
| | P. |
| | |
| | 6) P-1: THE 1/2-INCH HW SUPPLY PIPES TO THE PUBLIC |
| | LAVATORIES SHALL NOT EXCEED 2FT. TO TERMINATION FROM |
| | THE HW SOURCE PER TABLE C404.5.1 FBC ENERGY. IN ORDER |
| | TO MEET COMPLIANCE, PROVIDE EITHER A RECIRCULATION PUMP |
| | AND LINE, OR POINT OF USE WATER HEATERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |