| Plan Review Notes For Permit 23021403 |
| Permit Number |
23021403 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-07 10:58:04 | 1ST REVIEW FMC | | | PERMIT: 23021403 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY CALCULATIONS DO NOT SHOW THE NEW OVER | | | HEAD DOOR IN THE CALCULATIONS. PROVIDE ENERGY | | | CALCULATIONS INCLUDING THE OVERHEAD DOOR. FEC C402.5.4 | | | AND C402.5.6 | | | | | | 2) PROVIDE THE SMOKE DETECTORS IN THE SUPPLY DUCT FOR | | | EACH OF THESE RTU???S. THEY SHARE THE SUPPLY SO ARE | | | REQUIRED FMC 606.2.2 | | | | | | 3) PROVIDE A ROOF DRAWING INDICATING THE LOCATIONS OF | | | THE RTU???S AND GUARD PROTECTION IF REQUIRED BY FMC | | | 304.11 | | | | | | 4) INDICATE THE LOCATION OF THE ACCESS FOR THE RTU???S | | | ON THE ROOF DRAWING. FMC 306.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|