2023-03-01 10:08:49FIRE PROVISO COMMENTS:
  
 (1) AN EVALUATION OF THE FIRE SPRINKLER SYSTEM SHALL BE
 CONDUCTED BY A PROPERLY LICENSED FIRE SPRINKLER
 CONTRACTOR TO ENSURE THE EXISTING FIRE SPRINKLER SYSTEM
 IS ADEQUATE FOR THE PROPOSED OCCUPANCY AND COMMODITY
 CLASSIFICATION.
  
 (2) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE PERFORMED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 (3) THE EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (5) THE PLAN SUBMITTAL DID NOT INDICATE THE LOCATION OF
 THE NEAREST WATER SOURCE TO THE FIRE DEPARTMENT
 CONNECTION OF THE EXISTING FIRE SPRINKLER SYSTEM. THE
 LOCATION MUST MEET THE REQUIREMENTS OF NFPA 13.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  